3. Why Do High/Medium Voltage Distribution Equipment Need Arc Energy Absorbing Base?

High/medium voltage switchgear Arc Energy Absorbing Base is designed to catch, absorb, and directionally vent the enormous energy from internal short-circuit arcs—preventing cabinet explosion, personnel injury, and cascading fire damage. It is now a baseline standard for modern medium-voltage (10–35kV) internal arc-resistant design.

1. What High/Medium Voltage Switchgear Fears Most: Internal Arcing (Explosion-Level Energy)

When a phase-to-phase or phase-to-ground short circuit occurs inside a 10–35kV switchgear:

  • Arc temperature: 15,000–20,000°C (far exceeding the Sun's surface)
  • Pressure: tens to hundreds of kPa, erupting in milliseconds
  • Energy: can reach MJ levels, equivalent to a small explosion

Consequences:

  • Cabinet doors blown off, cabinet body torn apart (fatal accidents are common)
  • High-temperature gas and molten metal spray
  • Adjacent equipment ignited, entire busbar section disabled

Traditional top-only pressure relief panels cannot withstand high-current arcs (≥20kA)

Arc Energy Absorbing Base = an integrated "explosion-proof + energy-absorbing + pressure-relief" structure beneath the cabinet.

2. Four Irreplaceable Functions of Arc Energy Absorbing Base (Why It Is Essential)

(1) Absorbing Peak Pressure, Preventing Cabinet Explosion

  • Base incorporates metal honeycomb, corrugated, or grid energy-absorbing structures (or high-temperature damping materials)
  • Arc shock wave downward → base plastic deformation + friction + thermal dissipation → reduces peak pressure by 50%–80%
  • Protects cabinet body, doors, and bolts from being directly blown open
  • (Many legacy cabinet accidents: insufficient top relief causes explosion through the weakest point—the cabinet door)

(2) Directional Venting, Protecting Personnel, Not Spraying Toward Operating Face

  • Base features rear/bottom pressure relief channels, forcing high-temperature, high-pressure gas to vent rearward/downward
  • Prevents spraying toward cabinet doors (operating face), adjacent cabinets on both sides, or cable trench fronts
  • Complies with IEC 62271-200 / GB 3906 internal arc safety direction requirements: away from personnel

(3) Blocking Arc Root, Preventing Arc from "Burning Through Base and Entering Cable Trench"

  • Base uses high-temperature-resistant, flame-retardant, non-melt-through composite steel plates + fire-resistant coating
  • When arc propagates downward, the base isolates + cools + extinguishes, preventing:
  • Burning through the base plate → arc entering cable trench → igniting entire trench cables
  • Arc root transferring to cabinet frame → expanding fault, prolonging arc duration

(4) Protecting Cable Compartment, Protecting Secondary Circuits, Reducing Cascading Failures

  • Cable compartment is the most common location for internal arcing (joints, cable terminations, insulation aging)
  • Base absorbs shock, preventing cable compartment deformation, doors stuck shut, secondary wiring broken
  • Prevents the vicious cycle of "primary fault → secondary damage → protection failure → prolonged arc duration → larger explosion"

3. Traditional "Top-Only Relief" vs "Arc Energy Absorbing Base + Top Dual-Channel"

Solution Explosion Resistance Personnel Safety Adjacent Cabinet Safety Applicable Current
Top-only relief panel (legacy) Weak Poor (easily explodes through door) Poor ≤16kA, short duration
Absorbing base + top dual-channel Strong (80% peak reduction) Excellent (rear/downward venting) Excellent 20–40kA, 0.5–1s (modern standard)

Conclusion: For 20kA+ systems, critical loads, unmanned stations, and tunnel/corridor cabinets, an absorbing base is mandatory.

4. Standards and Regulatory Requirements (For Tender Documents / Technical Agreements)

  • IEC 62271-200: Medium-voltage switchgear internal arc protection, mandates pressure relief + energy absorption
  • GB 3906: High-voltage switchgear, internal arc test (IAC) essential structure
  • State Grid / Southern Grid anti-accident measures: New 10kV and above switchgear shall be equipped with internal arc absorbing base + directional pressure relief channel.

5. Summary

In summary, high/medium voltage distribution equipment must be equipped with an Arc Energy Absorbing Base because internal short-circuit arc energy is enormous and erupts in milliseconds, and top-only pressure relief is insufficient. The absorbing base absorbs peak pressure, directionally vents high-temperature gas, blocks arc downward propagation, and protects personnel and equipment. It is the key safety structure for meeting national/industry standards, preventing cabinet explosion and personnel injury, and stopping cascading fire damage.