SF6 Leakage Monitoring

Real-time monitoring of SF6 gas concentration, oxygen content, temperature and humidity, ensuring safe switchgear operation

Key Takeaways

  • SF6 leakage monitoring detects ppm-level concentration changes in GIS rooms and switchgear enclosures.
  • Continuous infrared or electrochemical sensing with alarm thresholds and trend logging to SCADA.
  • SF6 has a global warming potential of about 23,500, so early leak detection supports both personnel safety and emission compliance.
  • Zone-based sensor layout localises a leak to a compartment instead of an entire substation.

Product Introduction

The SF6 leak integrated monitoring system is a gas monitoring solution designed for high-voltage switchgear, capable of real-time monitoring of SF6 gas concentration, oxygen content, temperature and humidity inside the switchgear. Using infrared or ultrasonic principles for SF6 gas detection, it features high sensitivity and stability, promptly detecting SF6 gas leaks to ensure safe equipment operation and personnel health.

Product Features

  • Integrated design - multi-parameter monitoring of SF6, O2, temperature and humidity
  • Infrared/ultrasonic dual principle options to meet different scenario needs
  • RS485 communication interface, supporting remote monitoring and data transmission
  • Wide voltage supply 10-30V DC, adapts to complex on-site power environments
  • Compliant with GB/T8905-1996 and DL408-1991 standards

Applicable Scenarios

SF6 HV switchgear, GIS equipment, distribution rooms, substations, power equipment maintenance, etc.

Request Quote

Monitoring Background

Sulfur hexafluoride (SF6) is a colorless, odorless, non-toxic, non-flammable stable electronegative gas, stable at room temperature and pressure, but under arcing SF6 easily decomposes into highly corrosive and toxic gases such as SF4, S2F2, SF2, SOF2, SO2F2, SOF4, HF. SF6 gas density is about 5 times that of air, a typical asphyxiant; inhaling a mixture of 80% SF6 + 20% oxygen for several minutes causes limb numbness or even suffocation. SF6 gas damages the atmospheric ozone layer, intensifying the greenhouse effect and affecting climate change.

According to GB/T8905-1996 "Guidelines for Gas Management and Detection in SF6 Electrical Equipment", DL408-1991 "Electrical Safety Work Regulations" and "State Grid Corporation's 18 Major Anti-Accident Measures", distribution rooms with SF6 equipment must ensure SF6 concentration below 1000ppm, install forced ventilation, oxygen alarms and SF6 concentration detection alarms.

Additionally, during the incubation period of equipment faults, discharge may occur inside switchgear, converting oxygen in the air into ozone. Ozone is highly oxidizing, corroding and damaging electronic equipment in the room, affecting normal operation and service life. Long-term exposure to high ozone concentrations causes respiratory and skin problems. By monitoring ozone concentration changes in switchgear, discharge phenomena can be indirectly monitored to assess insulation status.

Technical Parameters

Basic Parameters

Power Supply 10-30V DC10-30V DC
Communication Interface RS485RS485
Power Consumption IR principle: 2.5W; Ultrasonic principle: 1.5W
Operating Environment -10~60℃, 0~95%RH non-condensing

SF6 Parameters

Range 0~1000ppm (default), 0-2000/3000ppm optional
Accuracy 0~1000ppm:±10%(@500ppm,60%RH,25℃);0~2000ppm:±10%(@2000ppm,60%RH,25℃)
Resolution 1ppm
Zero Drift ±3ppm
Response Time ≤30s
Stability ≤2% signal value/month
Warm-up Time ≥30min
Repeatability ≤3%

O2 Parameters

Range 0~30%VOL
Resolution 0.1%VOL
Accuracy ±3%FS
Repeatability ≤1%
Warm-up Time ≥5min
Response Time ≤10s
Stability ≤5% signal value/year
Service Life 2 years (default), 5 years, 10 years optional

Temperature & Humidity Parameters

Temperature Range -40℃~+80℃
Temperature Accuracy ±0.5℃(@25℃)
Humidity Range 0~99%RH
Humidity Accuracy ±3%RH(@60%RH,25℃)