Real-time monitoring of SF6 gas concentration, oxygen content, temperature and humidity, ensuring safe switchgear operation
The SF6 leak integrated monitoring system is a gas monitoring solution designed for high-voltage switchgear, capable of real-time monitoring of SF6 gas concentration, oxygen content, temperature and humidity inside the switchgear. Using infrared or ultrasonic principles for SF6 gas detection, it features high sensitivity and stability, promptly detecting SF6 gas leaks to ensure safe equipment operation and personnel health.
SF6 HV switchgear, GIS equipment, distribution rooms, substations, power equipment maintenance, etc.
Request QuoteSulfur hexafluoride (SF6) is a colorless, odorless, non-toxic, non-flammable stable electronegative gas, stable at room temperature and pressure, but under arcing SF6 easily decomposes into highly corrosive and toxic gases such as SF4, S2F2, SF2, SOF2, SO2F2, SOF4, HF. SF6 gas density is about 5 times that of air, a typical asphyxiant; inhaling a mixture of 80% SF6 + 20% oxygen for several minutes causes limb numbness or even suffocation. SF6 gas damages the atmospheric ozone layer, intensifying the greenhouse effect and affecting climate change.
According to GB/T8905-1996 "Guidelines for Gas Management and Detection in SF6 Electrical Equipment", DL408-1991 "Electrical Safety Work Regulations" and "State Grid Corporation's 18 Major Anti-Accident Measures", distribution rooms with SF6 equipment must ensure SF6 concentration below 1000ppm, install forced ventilation, oxygen alarms and SF6 concentration detection alarms.
Additionally, during the incubation period of equipment faults, discharge may occur inside switchgear, converting oxygen in the air into ozone. Ozone is highly oxidizing, corroding and damaging electronic equipment in the room, affecting normal operation and service life. Long-term exposure to high ozone concentrations causes respiratory and skin problems. By monitoring ozone concentration changes in switchgear, discharge phenomena can be indirectly monitored to assess insulation status.
| Power Supply | 10-30V DC10-30V DC |
| Communication Interface | RS485RS485 |
| Power Consumption | IR principle: 2.5W; Ultrasonic principle: 1.5W |
| Operating Environment | -10~60℃, 0~95%RH non-condensing |
| Range | 0~1000ppm (default), 0-2000/3000ppm optional |
| Accuracy | 0~1000ppm:±10%(@500ppm,60%RH,25℃);0~2000ppm:±10%(@2000ppm,60%RH,25℃) |
| Resolution | 1ppm |
| Zero Drift | ±3ppm |
| Response Time | ≤30s |
| Stability | ≤2% signal value/month |
| Warm-up Time | ≥30min |
| Repeatability | ≤3% |
| Range | 0~30%VOL |
| Resolution | 0.1%VOL |
| Accuracy | ±3%FS |
| Repeatability | ≤1% |
| Warm-up Time | ≥5min |
| Response Time | ≤10s |
| Stability | ≤5% signal value/year |
| Service Life | 2 years (default), 5 years, 10 years optional |
| Temperature Range | -40℃~+80℃ |
| Temperature Accuracy | ±0.5℃(@25℃) |
| Humidity Range | 0~99%RH |
| Humidity Accuracy | ±3%RH(@60%RH,25℃) |
Rapid arc energy absorption device inside switchgear, together with SF6 monitoring forms the equipment safety protection system.
Targeted elimination of PD sources in GIS and switchgear, combined with SF6 monitoring for comprehensive gas-insulated equipment management.
Insulated fiber optic temperature monitoring of HV equipment, complementing SF6 gas monitoring for comprehensive equipment status awareness.